Robot investigation of Fukushima units 1 and 3 gets under way

10 June 2012


A monitoring room at Fukushima Daiichi unit 3 has been found to exhibit high levels of radiation, although a visual inspection did not find any evidence of machinery damage. The examination of the unit 3 travelling in-core probe (TIP) room was planned to be carried out using a robot, but its damaged door, which had been blown off its hinges, blocked the robot's access. Instead a visual inspection was carried out. Radiation levels were found to be elevated (about 50 mSv/hr), about 10-20 times higher than at unit 2 (that survey data was originally released in March).

However an inspection using a robot designated "Packbot" has begun a systematic survey of radiation at the unit 1 ground floor using two dosimeters (mounted at heights of 50mm and 1500mm above the floor) and gamma cameras (which compare the radiation field to a photographic image). The gamma cameras were mounted on an inclinable mount that also rotates around the vertical axis. Surveys were taken every 3m. The cameras were inclined at 10, 50 and 90 degrees. The data will be used to create a continuous 3D contamination map. The survey is limited to accessible parts of the unit 1 ground floor, which excludes northern and southern zones, which are blocked, respectively, by gas processing equipment and shields that cannot be moved.

Dose rates measured were generally around 5 mSv/hr. Measurements in similar areas taken in late 2011 were higher, suggesting that the radiological contamination is decreasing. Further "manual" surveys of dust and core wall boring will begin later.




Linkedin Linkedin   
Privacy Policy
We have updated our privacy policy. In the latest update it explains what cookies are and how we use them on our site. To learn more about cookies and their benefits, please view our privacy policy. Please be aware that parts of this site will not function correctly if you disable cookies. By continuing to use this site, you consent to our use of cookies in accordance with our privacy policy unless you have disabled them.