Bouchain achieves 62.22% combined cycle efficiency

4 August 2016



EDF’s Bouchain combined cycle plant – the first commercial application of GE’s all-air-cooled 9HA gas turbine – achieved an efficiency of 62.22% (ISO conditions) during commissioning, a new world record, recognised as such by Guinness World Records. The previous best was 61.5%, set by the Siemens H class combined cycle plant at the Fortuna unit of Stadtwerke Düsseldorf’s Lausward power station (profiled in the May 2016 edition of Modern Power Systems).


And the 62.22% combined cycle efficiency, remarkable as it is, is “a beginning not an ending for us”, said Joe Mastrangelo, GE Power’s president and CEO of gas power systems. “We’ve got technology programmes turbine that take us above 63%, with a march to 65% SSS by the beginning of the next decade.”

The 605 MW Bouchain plant, “co- developed and designed” by GE and EDF, was officially inaugurated on 17 June.

Like Siemens, GE also emphasises the flexibility of its HA based combined cycle plants, reported to be capable of reaching full power from “cold standstill” in less than 30 minutes. This will be important for Bouchain (as for other combined cycle units struggling to make money in current European power market conditions), which is expected to operate for only 2500-3500 hours per year, with more than 100 starts/stops.

In addition GE sees Bouchain as a leading example of its “digital power plant” concept, with hundreds of extra sensors installed, providing “significant data capture”, according to Paul McElhinney president & CEO, GE Power Services. When combined with “the digital capability which the company has been building up over the past couple of years ”this is expected to help avoid unplanned outage, optimise operation and substantially reduce lifecycle O&M costs.

Bouchain’s minimum plant load (turndown) islessthan40%,whilearamprateofplusor minus 67 MW/min is achievable.

The plant can provide rapid response in the event of grid frequency drops, eg, 94 MW in 10 seconds/147 MW in 30 seconds.

NOx emissions are less than 50 mg/Nm3 and CO is less than 30 mg/Nm3.

Bouchain The completed Bouchain combined cycle plant
Bouchain The main equipment. The plant employs a single shaft configuration with integrated SSS clutch. The steam turbine has separate HP/IP/LP, while the generator is liquid cooled. The HRSG (heat recovery steam generator), supplied by CMI Energy, is of the horizontal- exhaust-flow type, with steam conditions of 170 barg/575°C. The plant uses the site’s existing cooling tower (see site photograph)
Bouchain The Bouchain site during construction of the record breaking combined cycle plant. The closed-down coal fired power plant can be seen to the right. The cooling tower is being re-used for the new unit


Linkedin Linkedin   
Privacy Policy
We have updated our privacy policy. In the latest update it explains what cookies are and how we use them on our site. To learn more about cookies and their benefits, please view our privacy policy. Please be aware that parts of this site will not function correctly if you disable cookies. By continuing to use this site, you consent to our use of cookies in accordance with our privacy policy unless you have disabled them.